MODELS                                         FT-C00800120016002400320040006000800100012001400
Specifications           
Heat Input1,000 BTU/HR19201,3791,8392,7593,6784,5986,8979,19511,49413,79316,092
1,000 KCAL/HR2323484636959271,1591,7382,3172,8973,4764,055
Heat Output1,000 BTU/HR8001,2001,6002,4003,2004,0006,0008,00010,00012,00014,000
1,000 KCAL/HR2003004006008001,0001,5002,0002,5003,0003,500
Thermal Fluid ContentGallons102119316876132201290383460
Liters3880721162582884986481,0971,4481,741
Recommended Flow RateGPM5075100150250250375500615730800
M3/HR11.41722.73456.856.885.2113.6139167182
Power           
Typical Circulating PumpHP1010151520203040505060
KW7.57.511.211.214.914.922.529.537.337.345
Typical Burner MotorHP1.533357.57.515202020
KW1.12.22.22.23.75.65.611.211.21515